IQ8Alarm Plus IP Sockel, weiß

806201

Approval: VdS

Addressable, completely bus powered and short circuit / open circuit resistant alarm signaling device compliant with EN 54-3. Provides up to 20 different programmable signaling tones including DIN tone in accordance with DIN 33404 Part 3 for acoustic and optical alarm signaling. The volume can be set to 8 different levels. Its flat design enables optimum adaptation to different interiors. It is made of shock and scratch resistant plastic. Optionally, bases 806201 and 806202 with side cable entry, knock-outs and weatherproof protection (IP65) can be installed.
  • Completely bus supplied alarm device
  • Powered loop compatible
  • Low power consumption
  • Up to 32 alarm devices for each powered loop
  • Each alarm device has built-in isolator
  • Tones can be used for other purposes in addition to warning of fire, making the device ideal for use in schools etc.
  • Soft start option, ideal for hospitals and nursing homes
Acoustic alarm signaling (dependent on type):
  • Acoustic pressure up to 99 dB(A) @ 1 m
  • Volume programmable in 8 steps via tools 8000
  • Up to 26 different languages are available
  • 20 different signaling tones, including DIN tone
  • Multilingual speech alarm in 5 different languages
  • Alarm signaling, evacuation, and test alarm can each be programmed in different languages
  • Speech alarm, 5 pre-programmed alarm texts and other country-typical alarm signals
Optical alarm signaling:
  • Flash intensity equivalent to 3W Xenon flash light
Additional Information:
Please consider:
  • Admissible maximum loop length
  • Admissible maximum number of single alarm device types
  • Maximum number of 127 bus devices for each loop Systems requirements: FACP IQ8Control from version V3.04 FACP FlexES Control esserbus-Plus functionality Programming software tools 8000 from version V1.09
Attention - an operation with the FACP'S 8000 C/M is not possible!!! For upgrading 8000 C/M control units, IQ8Lumivox signaling devices must be used. If required, please contact our returns department. For checking the battery capacity of FACP, the value “quiescent current @ FACP battery“ can be added.
Schutzart IP 56
Farbe
weiß, ähnlich RAL 9010
  • 806202 IP65 base, red

Publikationen - Produktdatenblätter

DatentypNameGröße
Produktinformation IQ8 Alarm Version: 09.2009 355 KB